Product Identification

  • Manufacturer: IMO Precision Controls.

  • Model: REDMOD20.

  • Product Type: Redundant Power Supply Module.

  • Nominal System Voltage: 24 VDC.

  • Input Configuration: Dual input.

  • Installation: DIN rail.

Input Specifications

  • Rated Input Voltage: 19–29 VDC.

  • Number of Inputs: 2.

  • Rated Input Current: 20 A continuous.

Output Specifications

  • Rated Output Current: 20 A.

  • Maximum Output Current: 30 A for 5 seconds.

  • Output Voltage Drop: 0.25 V.

  • Maximum Reverse Voltage: 30 V.

Status Monitoring and Protection

  • Green LED: Input DC OK indication.

  • Relay Contacts: DC OK monitoring.

  • Integrated Decoupling Diodes.

  • DC OK Contact Rating: 30 VDC / 1 A, resistive load.

  • Power Ready OK: Input above 20V (±5%) and below 30V (±5%).

  • Power Ready Fail: Input below 20V (±5%) or above 30V (±5%).

Electrical Insulation

  • Isolation Voltage: 100 VDC.

  • Isolation Resistance: 100 MΩ at 500 VDC.

Environmental and Mechanical Specifications

  • Ambient Operating Temperature: -40°C to +80°C.

  • Storage Temperature: -40°C to +85°C.

  • Relative Humidity: 5–95% RH.

  • Cooling Method: Natural convection.

  • Protection Rating: IP20.

  • Enclosure Material: Metal.

  • Dimensions: H125 × W32 × D100 mm.

  • Weight: 500 g.

  • Pollution Degree: 2.

  • MTBF: 792,000 hours.

Installation Requirements

  • DIN Rail: TS35/7.5 or TS35/15.

  • Wire Size: AWG 24–10 / 0.2–4 mm².

  • Copper Conductors: 60/75°C rated.

  • Recommended Wire Stripping Length: 8 mm.

  • Recommended Ventilation Clearance: 25 mm on all sides.

Input Terminal Assignment

  • Terminal 1: +Vin1.

  • Terminal 2: -Vin1.

  • Terminal 3: +Vin2.

  • Terminal 4: -Vin2.

Output and Signal Terminal Assignment

  • Terminals 1–2: Alarm1 DC OK.

  • Terminals 3–4: Alarm2 DC OK.

  • Terminals 5–6: FG.

  • Terminal 7: +Vout.

  • Terminal 8: -Vout.

The input and output terminal blocks have separate numbering systems. Always follow the manufacturer's wiring diagram.

 
technical.imopc.com+1

 

Typical Applications

  • 1+1 redundant power supply arrangements.

  • 1+N industrial power redundancy systems.

  • PLC and HMI power continuity.

  • Industrial control panel redundancy.

  • Sensor and automation equipment power distribution.

RPM20 Replacement Considerations

The supplied product information identifies REDMOD20 as the replacement for the discontinued RPM20. However, a manufacturer-issued direct replacement or pin-compatibility statement has not been independently verified.

Before replacing RPM20, verify electrical ratings, terminal assignments, physical dimensions, mounting requirements and power redundancy system configuration.